PHMSA Report 20150460
PHMSA Report 20150460
Hazardous liquid incident in ALVORD, WISE County, TX. Reported cause: CORROSION FAILURE. Reported consequences: 0 fatalities, 0 injuries, 0.24 CRUDE OIL released, $10,000 reported property damage. Operator-reported incident data submitted to PHMSA, generally within 30 days. Records may be supplemented or corrected and do not represent final agency causal findings.
Report number: 20150460.
Operator ID: 18718.
Reported incident date: 11/18/2015 8:00.
Location detail: 41.4
Cause detail: INTERNAL CORROSION
Cause detail: AT APPROXIMATELY 08:00 ON 11/18/2015, A COMPANY EMPLOYEE DISCOVERED AN APPROXIMATE 2 BBL RELEASE OF CRUDE OIL INSIDE ALVORD PUMP STATION. THE PUMP STATION WAS DOWN AND ISOLATED FROM THE MAINLINE PRIOR TO THE DISCOVERY OF THE RELEASE. THE EMPLOYEE THAT DISCOVERED THE RELEASE WAS ONSITE TO PERFORM A STATION REVIEW AND ASSESSMENT AND DID NOT HAVE RESPONSE MATERIALS AND EQUIPMENT AVAILABLE. THE AREA MANAGER WAS IMMEDIATELY ALERTED AND ADDITIONAL PERSONNEL AND RESOURCES WERE DISPATCHED TO THE SITE ARRIVING AT APPROXIMATELY 09:15 AS CLEANUP EFFORTS PROGRESSED IT WAS DISCOVERED THAT APROXIMATELY 10 GALLONS OF CRUDE OIL HAD MIGRATED TO A SMALL POND ADJACENT TO THE FACILITY DUE TO HEAVY RAIN THE NIGHT BEFORE. AT THIS TIME ADDITIONAL INTERNAL NOTIFICATIONS WERE MADE AND THE RELEASE WAS REPORTED TO THE NRC. THE OIL/WATER MIX WAS IMMEDIATELY REMOVED FROM THE POND VIA VACUUM TRUCK. ALL CONTAMINATED SOIL WAS EXCAVATED AND REMEDIATED ONSITE. INVESTIGATION OF THE FAILED SECTION REVEALED AN INTERNAL CORROSION PINHOLE IN THE DISCHARGE PIPING FROM THE PUMP AND A PLIDCO CLAMP WAS INSTALLWD. THIS PUMP STATION IS NO LONGER UTILIZED FOR NORMAL OPERATION OF THE PIPELINE AND AS SUCH THE AFFECTED PIPE AND OTHER STATION PIPING WILL REMAIN ISOLATED AND BYPASSED FROM THE MAINLINE. MODIFICATIONS ARE PLANNED THAT WILL REMOVE THE UNDERGROUND STATION PIPING AND BRING ALL ABOVE GRADE. THE FAILED SECTION OF PIPE WILL BE PERMANENTLY REMOVED VIA THIS PROJECT.
PHMSA trend classification: not significant, not serious.
PHMSA standardized cause: CORROSION — INTERNAL.
PHMSA indexed costs: $44,884 reported total cost, $22,516.814 in 1984 dollars, $55,451.982 in current-year dollars.
PHMSA trend flags, standardized causes, and indexed costs are analytical fields added to operator-reported incident data. They do not represent final agency causal findings.
This material provides agency context. It does not replace binding regulatory text, and its legal effect depends on the underlying authority and facts.