PHMSA Report 20120203
PHMSA Report 20120203
Hazardous liquid incident in BAKER, SAN BERNARDINO County, CA. Reported cause: EQUIPMENT FAILURE. Reported consequences: 0 fatalities, 0 injuries, 0.42 REFINED AND/OR PETROLEUM PRODUCT (NON-HVL) WHICH IS A LIQUID AT AMBIENT CONDITIONS released, $4,500 reported property damage. Operator-reported incident data submitted to PHMSA, generally within 30 days. Records may be supplemented or corrected and do not represent final agency causal findings.
Report number: 20120203.
Operator ID: 26125.
Reported incident date: 6/6/2012 0:31.
Location detail: 146.2
Cause detail: PUMP OR PUMP-RELATED EQUIPMENT
Cause detail: AT APPROXIMATELY 2240 (10:40 PM LOCAL TIME) ON JUNE 5, 2012, THE CONTROL CENTER RECEIVED A PUMP SEAL FAILURE ALARM AT BAKER BOOSTER STATION AND PUMP #4 SHUTDOWN AUTOMATICALLY. THE ALARM CLEARED, THERE WERE NO OTHER ALARMS (NO SUMP ALARM), AND PRESSURES WERE NORMAL INDICATING EITHER A SMALL AMOUNT OF PRODUCT STAYING WITHIN THE CLOSED SYSTEM OR A FALSE ALARM. AFTER RESTARTING, A DECISION WAS MADE BY FIELD MANAGEMENT TO SHUTDOWN THE SYSTEM AND DISPATCH A TECHNICIAN TO THE PUMP STATION. WHILE IN THE PROCESS OF SHUTTING DOWN THE UNIT THE CONTROLLER RECEIVED A HIGH SUMP ALARM. THE CONTROLLER THEN ISOLATED THE PUMP AND STATION BY CLOSING APPROPRIATE VALVES. AT APPROXIMATELY 0031 AFTER TURNING ON STATION LIGHTING, THE TECHNICIAN IDENTIFIED TWO STAINS ON THE GROUND WITH DIMENSIONS 4 FT. X 13 FT. AND 5 FT. X 3 FT. LATER INVESTIGATION DETERMINED THE CAUSE OF THE RELEASE AS FAILURE (ATYPICAL ' FAILED WITHIN 6 MONTHS OF INSTALLATION) OF THE INBOARD PUMP SEAL. THE TECHNICIAN AND CONTRACTOR SUPPORT TEAM REPLACED THE SEAL ON 6/11/12. APPROXIMATELY 17.6 GALLONS (0.42 BBLS) OF TURBINE FUEL WAS RELEASED AND THE CONTAMINATED SOIL* AND PRODUCT WAS PROPERLY REMOVED FROM THE SITE. * AFTER REMOVING THE 'WET' CONTAMINATED SOIL, ADDITIONAL CONTAMINATED SOIL WAS DISCOVERED. THIS 'OLDER' CONTAMINATED SOIL IS THOUGHT TO BE FROM AN HISTORICAL RELEASE. NOTE: PART A, #4, THIS IS THE TIME OF DISCOVERY BY THE TECHNICIAN. THE LEAK PROBABLY OCCURRED AT APPROXIMATELY 2240. NOTE: PART A, #9 AND 11 DETERMINED FROM DIMENSIONS OF STAINED SOIL.
PHMSA trend classification: not significant, not serious.
PHMSA standardized cause: EQUIPMENT FAILURE — PUMP/COMPRESSOR OR PUMP/COMPRESSOR-RELATED EQUIPMENT.
PHMSA indexed costs: $11,049 reported total cost, $5,819.508 in 1984 dollars, $14,331.658 in current-year dollars.
PHMSA trend flags, standardized causes, and indexed costs are analytical fields added to operator-reported incident data. They do not represent final agency causal findings.
This material provides agency context. It does not replace binding regulatory text, and its legal effect depends on the underlying authority and facts.