PHMSA Report 20130041
PHMSA Report 20130041
Gas transmission and gathering incident in DECATUR, DEKALB County, GA. Reported cause: EXCAVATION DAMAGE. Reported consequences: 0 fatalities, 0 injuries, 365 NATURAL GAS released, $44,000 reported property damage. Operator-reported incident data submitted to PHMSA, generally within 30 days. Records may be supplemented or corrected and do not represent final agency causal findings.
Report number: 20130041.
Operator ID: 792.
Reported incident date: 4/17/2013 10:50.
Location detail: INTERSECTION
Cause detail: EXCAVATION DAMAGE BY OPERATOR'S CONTRACTOR (SECOND PARTY)
Cause detail: EXCAVATION ISSUE
Cause detail: EXCAVATOR FAILED TO MAINTAIN CLEARANCE AFTER VERIFYING MARKS
Cause detail: OPERATOR'S CONTRACTOR WAS ATTEMPTING TO INSTALL APPROXIMATELY 200 FEET OF 24-INCH STEEL PIPE VIA CONVENTIONAL JACK & BORE WHERE IT APPEARS THE AUGER STRUCK A ROCK ABOUT 30-FEET INTO THE BORE AND VEERED APPROXIMATELY 3-FEET OFF THE BORE PATH STRIKING THE SIDE OF AN EXISTING 16-INCH HIGH PRESSURE STEEL TRANSMISSION PIPELINE CAUSING A LEAK. THE DAMAGE OCCURRED ON THE VERTICAL PIPE WHERE THE 16-INCH TRANSMISSION PIPELINE MADE A DEPTH CHANGE FROM 5-FEET TO 10-FEET DEEP.
PHMSA trend classification: not significant, not serious.
PHMSA standardized cause: EXCAVATION DAMAGE — OPERATOR/CONTRACTOR EXCAVATION DAMAGE.
PHMSA indexed costs: $66,696 reported total cost, $34,993.036 in 1984 dollars, $84,481.901 in current-year dollars.
PHMSA trend flags, standardized causes, and indexed costs are analytical fields added to operator-reported incident data. They do not represent final agency causal findings.
This material provides agency context. It does not replace binding regulatory text, and its legal effect depends on the underlying authority and facts.