Page 1U.S. Department of Transportation Pipeline and Hazardous Materials Safety Administration 1200 New Jersey Avenue, SE Washington, DC 20590 October 13, 2020 Oliver Sánchez Muñoz R&D Engineer Johnson Controls Josep Ros i ros, Naves 23. P.I. La Clota. 08740 Sant Andreu de la Barca, Spain Reference No. 20-0057 Dear Mr. Muñoz: This letter is in response to your August 4, 2020, email requesting clarification of the Hazardous Materials Regulations (HMR; 49 CFR Parts 171-180) applicable to service equipment for United Nations (UN) cylinders as it relates to certain ISO standards. You state you have a UN cylinder filled with a liquid extinguishing agent charged with a compressed gas, and the cylinder is equipped with pressure gauges and switches mounted to a quick release valve. Furthermore, you reference ISO 17871:2015, incorporated by reference in § 173.301b(c), and you indicate your understanding that section 4.2.6 of this standard provides additional requirements to those in ISO 10297:2014 as it relates to specification standards for service equipment under § 178.71(d). You also note that a recent update to ISO 17871 (2020) indicates that the valve burst test pressure is to be calculated at 1.5 times the valve test pressure, which is consistent with the same requirement for liquefied gases in ISO 10297:2014. Finally, you note your understanding that the instruction in section 4.2.6 of ISO 17871:2015 is that the valve test pressure must be at least the developed pressure of a full gas cylinder at 65 °C and will never exceed the test pressure of the pressure receptacle (i.e., the UN cylinder). You ask whether pressure gauges and switches mounted to quick release valves covered under ISO 17871:2015 comply with the hydraulic burst pressure test requirement when successfully tested (e.g., no visible deformation or burst) at 1.5 times the developed pressure of a full gas cylinder at 65 °C regardless of the test pressure marked on the cylinder. The answer to your question is no. The pressure gauge and switches mounted to the quick release valve must meet the burst test requirement of the cylinder that is being used. Furthermore, for purposes of performing the hydraulic burst pressure test in ISO 10297:2014, the formula you describe is used to determine the value of the burst test pressure. However, for purposes of § 178.71(d)(1), UN pressure receptacle equipment (e.g., a quick release valve) that is subjected to pressure must be designed and constructed to withstand at least 1.5 times the test pressure of the pressure receptacle. Therefore, if the calculated valve burst test pressure is less#
Page 2than 1.5 times the marked cylinder test pressure, the performance standard of § 178.71(d)(1) would not be achieved. Please also note that for purposes of ISO 10297:2014, section 6.3, valves designed to incorporate pressure gauges or pressure indicators must have the devices installed for testing, except for the hydraulic burst pressure test. I hope this information is helpful. Please contact us if we can be of further assistance. Sincerely, Dirk Der Kinderen Chief, Standards Development Branch Standards and Rulemaking Division#
Page 3Baker 20-0057 From: Oliver Sanchez Muñoz To: INFOCNTR (PHMSA); Baker, Yul (PHMSA) Cc: Dodd, Alice (PHMSA); Carlos Perez Perez Subject: 20-0029 Date: Tuesday, August 4, 2020 9:28:13 AM Attachments: 20-0029 Letterhead.pdf Importance: High CAUTION: This email originated from outside of the Department of Transportation (DOT). Do not click on links or open attachments unless you recognize the sender and know the content is safe. Dear Yul, Dear Sirs, We have received the attached letter of interpretation. Going little deeper on the details of that letter, we came to the following exposed approach. Please see below explanation and additional question we would like you to answer. Thanks. Your letter reference No 20-0029 in response to our letter dated April 1, 2020, are referring to final rule HM-215O published by PHMSA where ISO10297:2014 is incorporated by reference. It should be noted that also ISO17871:2015 has also been incorporated by the mentioned final rule. The application we are looking at is liquid extinguishing agents charged with compressed gases and pressure gauges and pressure switches that are mounted on valves covered by ISO17871 (quick release valves). ISO17871:2015, 4.2.6 introduces additional requirements to ISO10297:2014, 6.6.2. According to this additional requirements Pvt (valve test pressure) is determined as the developed pressure of a full gas cylinder at 65ºC and this pressure shall never exceed the test pressure of the pressure receptacle. Pvbt is typically calculated as 1.5 times Pvt. So in these cases the reference to the test pressure marked on the cylinder may not be applicable. NOTE: ISO17871:2020 4.2.7 (recently published), though not included of HM215O, fills a potential gap on how Pvbt is to be calculated, establishing that Pvbt for extinguishing agents charged with compressed gases is to be calculated as 1.5 time Pvt as for liquefied gases. NOTE: The developed pressure of a full gas cylinder at 65ºC shall never exceed the test pressure of the pressure receptacle. So, taken the above into consideration and given that now ISO10297:2014 and ISO17871:2015 have been incorporated by reference and restricting the scope of the question number 1 that was originally posed to this specific case, we ask the following: QUESTION:#
Page 4For liquid extinguishing agents charged with compressed gases, do pressure gauges and pressure switches mounted on valves covered by ISO17871:2015 as service equipment for UN cylinders comply the hydraulic burst pressure test requirement when successfully tested (no visible deformation or burst) at 1.5 times the developed pressure of a full gas cylinder at 65ºC, regardless of the test pressure marked in the cylinder. Best regards / Atentamente, Oliver Sánchez Muñoz R&D Engineer Johnson Controls +34 673838438 direct oliver.sanchez.munoz@jci.com @johnsoncontrols.com www.johnsoncontrols.com Johnson Controls Josep Ros i ros, Naves 23. P.I. La Clota. 08740 Sant Andreu de la Barca Spain THIS MESSAGE MAY CONTAIN INFORMATION THAT IS PRIVILEGED AND CONFIDENTIAL. The information contained in, or attached to, this message is intended solely for the use of the specific person(s) named above. If you are not the intended recipient then you have received this communication in error and are prohibited from review, retransmission, taking any action in reliance upon, sharing the content of, disseminating or copying this message and any of the attachments in any way. If you have received this communication in error, please contact the sender immediately and promptly delete this message from all types of media and devices. Thank you.#
This material provides agency context. It does not replace binding regulatory text, and its legal effect depends on the underlying authority and facts.