PHMSA 23-287179
PACIFIC GAS & ELECTRIC CO — Integrity Assurance Notification
MAOP RECONFIRMATION METHOD 6Pacific Gas and Electric Company (PG&E) has performed a comprehensive evaluation of all features at its Milpitas Terminal to reconfirm Maximum Allowable Operating Pressure (MAOP).1 This station is in Milpitas, California and supplies pressure and BTU controlled gas to the San Francisco Peninsula and the San Jose area. PG&E’s initial phase of this project identified all traceable, verifiable, and complete (TVC) records to reconfirm MAOP based on design and pressure test records. One (1) joint at the Milpitas Terminal was identified as having non-TVC records of a pressure test2 in this review. The joint considered in this evaluation is located in a high consequence area (HCA) and is located in a Class 3 location. PG&E proposes to establish a TVC MAOP record via 49 Code of Federal Regulations (CFR) §192.624(c)(3), Method 3.3#