49 CFR 192.359
Customer meter installations: Operating pressure.
Current as of 2026-08-18 Government source
eCFR editorial compilationAuthoritative but unofficial
View source (a)A meter may not be used at a pressure that is more than 67 percent of the manufacturer's shell test pressure.#
(b)Each newly installed meter manufactured after November 12, 1970, must have been tested to a minimum of 10 p.s.i. (69 kPa) gage.#
(c)A rebuilt or repaired tinned steel case meter may not be used at a pressure that is more than 50 percent of the pressure used to test the meter after rebuilding or repairing.#