P-80-027
P-80-027
NTSB safety recommendation P-80-027.
THE NTSB RECOMMENDS THAT THE RESEARCH AND SPECIAL PROGRAMS ADMINISTRATION: REQUIRE THAT ALL BUILDINGS AND SIMILAR ENCLOSURES WITHIN LNG FACILITIES CONNECTED BY PIPING OR CONDUIT BE FITTED WITH AN EFFECTIVE MEANS FOR DETECTING LNG VAPORS AND ALERTING COMPANY PERSONNEL.
Priority: CLASS II
Overall Status: Closed - Acceptable Action
Issued Date: 1980-05-07
Adopted Date: 1980-04-16
Overall Date Closed: 1981-05-07
Synopsis: ON OCTOBER 6, 1979, AN EXPLOSION CAUSED BY LIQUEFIED NATURAL GAS (LNG) VAPORS DESTROYED A TRANSFORMER BUILDING AT THE RECEPTION FACILITY OF THE COLUMBIA LNG CORPORATION, COVE POINT, MARYLAND. ODORLESS LIQUEFIED NATURAL GAS LEAKED THROUGH AN INADEQUATELY TIGHTENED LNG PUMP SEAL, VAPORIZED, PASSED THROUGH APPROXIMATELY 210 FT OF UNDERGOUND ELECTRICAL CONDUIT AND ENTERED THE SUBSTATION BUILDING. ONE PERSON WAS KILLED, AND ONE PERSON WAS SERIOUSLY INJURED. DAMAGE TO THE FACILITY WAS ESTIMATED AT ABOUT $3 MILLION.
Ntsbnumber: DCA80MP001
Report Number: PAR-80-02
Addressee Name: RSPA
Addressee Status: Closed - Acceptable Action
Addressee Date Closed: 1981-05-07
Addressee Acronym: RSPA
Addressee Organization Type: G-Federal Government
Communication Date: 1981-01-26
Communication Type: Official Correspondence
Communication Contents: RESEARCH AND SPECIAL PROGRAMS ADMINISTRATION LTR: SECTION 193.2819(F) OF THE NEWLY PUBLISHED REGULATIONS REQUIRES THAT ALL ENCLOSED BUILDINGS BE CONTINUOUSLY MONITORED FOR COMBUSTIBLE GAS, USING INSTRUMENTATION EQUIPPED WITH AUDIBLE OR VISIBLE ALARMS. CONSISTENT WITH THIS RECOMMENDATION, PART 193 ALSO REQUIRES THAT OTHER AREAS IN AN LNG PLANT WHERE FLAMMABLE FLUIDS COULD CREATE A HAZARD MUST BE CONTINUOUSLY MONITORED AS WELL.
Addressee Acronym: RSPA
Addressee Organization Type: G-Federal Government
Communication Date: 1981-05-07
Communication Type: Official Correspondence