16 NYCRR 255.121
255.121 Design of plastic pipe.
(a)Design formula. Design formulas for plastic pipe are determined in accordance with either of the following formulas:#
P = 2StDF/(D − t)#
P = 2SDF/(SDR − 1)#
Where:#
P = Design pressure, gauge, psig (kPa).#
S = For thermoplastic pipe, the hydrostatic design basis (HDB) is determined in accordance with the listed specification at a temperature equal to 73°F (23°C), 100° F (38°C), 120°F (49°C), or 140°F (60°C). In the absence of an HDB established at the specified temperature, the HDB of a higher temperature may be used in determining a design pressure rating at the specified temperature by arithmetic interpolation using the procedure in Part D.2 of PPI TR-3/2012, (incorporated by reference, see section 255.7 of this Part). For reinforced thermosetting plastic pipe, 11,000 psig (75,842 kPa).#
t = Specified wall thickness, inches (mm).#
D = Specified outside diameter, inches (mm).#
SDR = Standard dimension ratio, the ratio of the average specified outside diameter to the minimum specified wall thickness, corresponding to a value from a common numbering system that was derived from the American National Standards Institute (ANSI) preferred number series 10.#
DF = Design Factor, a maximum of 0.32 unless otherwise specified for a particular material in this section.#
(1)Except as provided in subdivisions (c) through (f) of this section, the design pressure for plastic pipe may not exceed a gauge pressure of 100 psig (689 kPa) for pipe used in:#
(i)distribution systems; or#
(ii)transmission lines in Class 3 and 4 locations.#
(2)Plastic pipe may not be used where operating temperatures of the pipe will be:#
(i)below -20°F (-29°C), or below -40°F (-40°C) if all pipe and pipeline components whose operating temperature will be below -20°F (-29°C) have a temperature rating by the manufacturer consistent with that operating temperature; or#
(ii)above the temperature at which the HDB used in the design formula under this section is determined.#
(3)Unless specified for a particular material in this section, the wall thickness of plastic pipe may not be less than 0.062 inches (1.57 millimeters).#
(4)All plastic pipe must have a listed HDB in accordance with PPI TR-4/2012 (incorporated by reference, see section 255.7 of this Part).#
(1)For PE pipe produced after July 14, 2004, but before January 22, 2019, a design pressure of up to 125 psig may be used, provided:#
(i)the material designation code is PE2406 or PE3408;#
(ii)the pipe has a nominal size (iron pipe size [IPS] or copper tubing size [CTS]) of 12 inches or less (above nominal pipe size of 12 inches, the design pressure is limited to 100 psig); and#
(iii)the wall thickness is not less than 0.062 inches (1.57 millimeters).#
(2)For PE pipe produced after January 22, 2019, a DF of 0.40 may be used in the design formula, provided:#
(i)the design pressure does not exceed 125 psig;#
(ii)the material designation code is PE2708 or PE4710;#
(iii)the pipe has a nominal size (IPS or CTS) of 12 inches or less; and#
(iv)The wall thickness for a given outside diameter is not less than that listed in the following table:#
Pipe size (inches) | Minimum wall thickness (inches) | Corresponding SDR (values) 1/2″ CTS | 0.090 | 7 3/4″ CTS | 0.090 | 9.7 1/2″ IPS | 0.090 | 9.3 3/4″ IPS | 0.095 | 11 1″ CTS | 0.119 | 11 1″ IPS | 0.119 | 11 1 1/4″ IPS | 0.151 | 11 1 1/2″ IPS | 0.173 | 11 2″ | 0.216 | 11 3″ | 0.259 | 13.5 4″ | 0.265 | 17 6″ | 0.315 | 21 8″ | 0.411 | 21 10″ | 0.512 | 21 12″ | 0.607 | 21#
(1)For PA-11 pipe produced after January 23, 2009, but before January 22, 2019, a DF of 0.40 may be used in the design formula, provided:#
(i)the design pressure does not exceed 200 psig;#
(ii)the material designation code is PA32312 or PA32316;#
(iii)the pipe has a nominal size (IPS or CTS) of 4 inches or less; and#
(iv)the pipe has a standard dimension ratio of SDR-11 or less (i.e., thicker wall pipe).#
(2)For PA-11 pipe produced on or after January 22, 2019, a DF of 0.40 may be used in the design formula, provided:#
(i)the design pressure does not exceed 250 psig;#
(ii)the material designation code is PA32316;#
(iii)the pipe has a nominal size (IPS or CTS) of 6 inches or less; and#
(iv)the minimum wall thickness for a given outside diameter is not less than that listed in the following table:#
Pipe size (inches) | Minimum wall thickness (inches) | Corresponding SDR (values) 1/2″ CTS | 0.090 | 7 3/4″ CTS | 0.090 | 9.7 1/2″ IPS | 0.090 | 9.3 3/4″ IPS | 0.095 | 11 1″ CTS | 0.119 | 11 1″ IPS | 0.119 | 11 1 1/4″ IPS | 0.151 | 11 1 1/2″ IPS | 0.173 | 11 2″ | 0.216 | 11 3″ | 0.259 | 13.5 4″ | 0.333 | 13.5 6″ | 0.491 | 13.5#
(e)Polyamide (PA-12) pipe requirements. For PA-12 pipe produced after January 22, 2019, a DF of 0.40 may be used in the design formula, provided:#
(1)the design pressure does not exceed 250 psig;#
(2)the material designation code is PA42316;#
(3)the pipe has a nominal size (IPS or CTS) of 6 inches or less; and#
(4)the minimum wall thickness for a given outside diameter is not less than that listed in the following table:#
Pipe size (inches) | Minimum wall thickness (inches) | Corresponding SDR (values) 1/2″ CTS | 0.090 | 7 3/4″ CTS | 0.090 | 9.7 1/2″ IPS | 0.090 | 9.3 3/4″ IPS | 0.095 | 11 1″ CTS | 0.119 | 11 1″ IPS | 0.119 | 11 1 1/4″ IPS | 0.151 | 11 1 1/2″ IPS | 0.173 | 11 2″ | 0.216 | 11 3″ | 0.259 | 13.5 4″ | 0.333 | 13.5 6″ | 0.491 | 13.5#
(1)Reinforced thermosetting plastic pipe may not be used at operating temperatures above 150°F (66°C).#
(2)The wall thickness for reinforced thermosetting plastic pipe may not be less than that listed in the following table:#
Nominal size in inches (millimeters) | Minimum wall thickness in inches (millimeters) 2 (51) | 0.060 (1.52) 3 (76) | 0.060 (1.52) 4 (102) | 0.070 (1.78) 6 (152) | 0.100 (2.54)#