HAR 6-77-132
HAR 6-77-132 External corrosion control: test leads
Current as of 1994-09-03 Government source
Hawaii Public Utilities CommissionOfficial agency material
View source connected to the pipeline so as to remain mechanically secure and electrically conductive.#
(b)Each test lead wire must be attached to the pipeline so as to minimize stress concentration on the pipe.#
(c)Each bared test lead wire and bared metallic area at point of connection to the pipeline must be coated with an electrical insulating material compatible with the pipe coating and the insulation of the wire. [Eff 49#
C.F.R. '192.471, October 1, 1990) ] (Auth: HRS '269-6) (Imp:#