HAR 6-77-34 Temperature derating factor (T) for steel pipe
Current as of 1994-09-03 Government source
Hawaii Public Utilities CommissionOfficial agency material
View source factor to be used in the design formula in section 6-77-29 is determined as follows: _____________________________________________________________________ │Temperature │derating Gas temperature in degrees Fahrenheit │factor (T) │ 250 or less.............................................│ 1.000 300.....................................................│ 0.967 350.....................................................│ 0.933 400.....................................................│ 0.900 450.....................................................│ 0.867 │ For intermediate gas temperatures, the derating factor is determined by interpolation. [Eff ] (Auth: HRS '269-6) (Imp: 49#