Regulationcurrent
HAR 6-77-197
HAR 6-77-197 Vault maintenance
Current as of 1994-09-03 Government source
Hawaii Public Utilities CommissionOfficial agency material
View source pressure limiting equipment, and having a volumetric internal content of 200 cubic feet or more, must be inspected at intervals not exceeding fifteen months, but at least once each calendar year, to determine that it is in good physical condition and adequately ventilated.#
(b)If gas is found in the vault, the equipment in the vault must be inspected for leaks, and any leaks found must be repaired.#
(c)The ventilating equipment must also be inspected to determine that it is functioning properly.#
(d)Each vault cover must be inspected to assure that it does not present a hazard to public safety. [Eff ] (Auth: HRS '269-6) (Imp: 49#