RCSA § 16-280b-A44
Excess flow valve testing
Current as of 2025-06-11 Government source
Connecticut Public Utilities Regulatory AuthorityOfficial agency material
View source (a)Each Operator shall test the functionality of Service Line excess flow valves at the time of installation in all locations where a test can be performed safely, and the operating pressure is adequate to perform the test.#
(b)The test shall consist of introducing a medium through the excess flow valve at a high flow rate, verifying shutoff, and resetting the device.#
(c)If the excess flow valve does not operate as designed, it shall be replaced immediately.#