RCSA § 16-280b-B20
Pressure testing
(a)Any pressure test performed pursuant to 49 CFR 192, Subpart J, as amended from time to time, shall:#
(1)be conducted using a gauge such that the test pressure is in the middle third of the range of the gauge;#
(2)be conducted at a test pressure of at least 150 percent of the desired MAOP or 90 pounds per square inch gauge, whichever is greater;#
(3)not be conducted against any valve separating the section being pressure tested from a Pipeline containing Gas, unless approved by the Authority in writing; and#
(4)be of a minimum duration in accordance with 49 CFR 192, Subpart J, as amended from time to time, or Table B20-1, whichever is greater. Table B20-1 - Minimum Pressure Test Duration Nominal Pipe Diameter (Inches) 30 Pipeline Length#
(feet)2 and less >2 to <8 8 and up < 200 15 min 30 min 1 hour 200 to <1,000 30 min 2 hours 4 hours 4 hours 6 hours 1,000 to <2,500 1 hour 2,500 to 5,000 2 hours 6 hours 12 hours * > 5,000 3 hours 8 hours * 24 hours * * A leakage survey shall be conducted between 3 and 14 calendar days after the Pipeline is pressurized with Gas.#
(b)Prior to applying any pressure test medium, the Pipeline being tested shall be opened to atmosphere to verify that no positive Gas pressure exists in the section to be tested.#
(c)The pressure test medium shall not be Gas when pressure testing a section of existing Low Pressure Main to allow for operation at High Pressure.#