LAC 43:XIII §2936
Compressor Stations: Gas Detection [49 CFR 192.736]
(A)A. Not later than September 16, 1996, each compressor building in a compressor station must have a fixed gas detection and alarm system, unless the building is: [49 CFR 192.736(a)]#
(1)1. constructed so that at least 50 percent of its upright side area is permanently open; or [49 CFR 192.736(a)(1)]#
(2)2. located in an unattended field compressor station of 1,000 horsepower (746 kW) or less. [49 CFR 192.736(a)(2)]#
(B)B. Except when shutdown of the system is necessary for maintenance under Subsection C of this Section, each gas detection and alarm system required by this Section must: [49 CFR 192.736(b)]#
(1)1. continuously monitor the compressor building for a concentration of gas in air of not more than 25 percent of the lower explosive limit; and [49 CFR 192.736(b)(1)]#
(2)2. if that concentration of gas is detected, warn persons about to enter the building and persons inside the building of the danger. [49 CFR 192.736(b)(2)]#
(C)C. Each gas detection and alarm system required by this Section must be maintained to function properly. The maintenance must include performance tests. [49 CFR 192.736(c)]#
AUTHORITY NOTE: Promulgated in accordance with R.S. 30:501 et seq.#
HISTORICAL NOTE: Promulgated by the Department of Natural Resources, Office of Conservation, LR 21:824 (August 1995), amended LR 27:1549 (September 2001), LR 30:1270 (June 2004).#