Regulationcurrent
LAC 43:XIII §7921
Testing Transfer Hoses [49 CFR 193.2621]
Current as of source date Government source
Louisiana Office of ConservationOfficial agency material
View source (A)A. Hoses used in LNG or flammable refrigerant transfer systems must be:#
(1)1. tested once each calendar year, but with intervals not exceeding 15 months, to the maximum pump pressure or relief valve setting; and [49 CFR 193.2621(a)]#
(2)2. visually inspected for damage or defects before each use. [49 CFR 193.2621(b)]#
AUTHORITY NOTE: Promulgated in accordance with R.S. 30:551.C.#
HISTORICAL NOTE: Promulgated by the Department of Natural Resources, Office of Conservation, LR 44:1057 (June 2018).#