LAC 43:XIII §7181
Impoundment Capacity: LNG Storage Tanks [49 CFR 193.2181]
(A)A. Each impounding system serving an LNG storage tank must have a minimum volumetric liquid impoundment capacity of:#
(1)1. 110 percent of the LNG tank's maximum liquid capacity for an impoundment serving a single tank; [49 CFR 193.2181(a)]#
(2)2. 100 percent of all tanks or 110 percent of the largest tank's maximum liquid capacity, whichever is greater, for the impoundment serving more than one tank; or [49 CFR 193.2181(b)]#
(3)3. if the dike is designed to account for a surge in the event of catastrophic failure, then the impoundment capacity may be reduced to 100 percent in lieu of 110 percent. [49 CFR 193.2181(b)]#
AUTHORITY NOTE: Promulgated in accordance with R.S. 30:551.C.#
HISTORICAL NOTE: Promulgated by the Department of Natural Resources, Office of Conservation, LR 44:1052 (June 2018).#