LAC 43:XIII §915
Temperature Derating Factor (T) for Steel Pipe [49 CFR 192.115]
Current as of source date Government source
Louisiana Office of ConservationOfficial agency material
View source (A)A. The temperature derating factor to be used in the design formula in §905 is determined as follows.#
Gas Temperature in Degrees Fahrenheit (Celsius)#
Temperature Derating Factor (T)#
250F (121C) or less#
1. 000#
300F (149C)#
0. 967#
350F (177C)#
0. 933#
400 F (204C)#
0. 900#
450F (232C)#
0. 867#
(B)B. For intermediate gas temperatures, the derating factor is determined by interpolation. [49 CFR 192.115]#