LAC 43:XIII §1925
Service Lines: Plastic [49 CFR 192.375]
(A)A. Each plastic service line outside a building must be installed below ground level, except that: [49 CFR 192.375(a)]#
(1)1. it may be installed in accordance with §1721.G; and [49 CFR 192.375(a)(1)]#
(2)2. it may terminate above ground level and outside the building, if: [49 CFR 192.375(a)(2)]#
(a)a. the above ground level part of the plastic service line is protected against deterioration and external damage; [49 CFR 192.375(a)(2)(i)]#
(b)b. the plastic service line is not used to support external loads; and [49 CFR 192.375(a)(2)(ii)]#
(c)c. the riser portion of the service line meets the design requirements of §1164. [49 CFR 192.375(a)(2)(iii)]#
(B)B. Each plastic service line inside a building must be protected against external damage. [49 CFR 192.375(b)]#